Nexans H07V-R 1x6 BLUE D1200m
Certifications and labels
Environmental data
Nexans H07V-R 1x6 BLUE D1200m
H07V-R are insulated stranded copper conductors, used for fixed protected installations indoors for power supply or lightings (from offices, domestic or commercial buidings...) with voltage up to 1000V AC or 750V DC.
Czytaj więcej- Nexans ref. : 10164438
Opis
Opis
Standardy
-
ProductEN 50525-2-31; EN 50575; HD 21.3; IEC 60227-1; IEC 60228; NF C32-201/3
-
InstallationNF C15-100
-
TestIEC 60332-1-2
Application
Nexans H07V-R is intended for fixed and protected electrical installations in dry environments, for main distribution and power circuits in conductor cross-sections of 6 mm² and above (excluding fire safety circuits):
- Multi-residential and commercial buildings: main distribution between the main switchboard and sub-distribution boards.
- Electrical switchboards and cabinets: internal wiring of large cross-sections, power feeders, and busbar connections.
- Technical rooms: connection of power equipment (main LV switchboards, control cabinets, and distribution enclosures).
For 1.5 mm² and 2.5 mm² conductor sizes: use H07V-U (Class 1 solid conductor).
For fire safety circuits (fire detection and alarm systems, emergency lighting, smoke extraction systems): use CR1-C1.
For installations requiring enhanced fire performance: use H07Z1-U/R/K (halogen-free).
Installation
Permitted laying options
- In free air on insulating supports, in dry locations
- Installed in trunking, skirting ducts, conduits, sleeves or cable trays
- In conduits (surface-mounted or concealed within dry walls)
- Internal wiring of electrical switchboards, cabinets and enclosures
Not suitable for
- Direct outdoor installation – PVC insulation is not resistant to UV exposure or weathering
- Damp, wet or waterlogged environments – moisture protection limited to AD1 conditions
- Direct burial without additional mechanical protection
- Mobile applications or repeated flexing – use H07V-K (Class 5 flexible conductor) or H07Z1-K instead
Installation parameters
- Minimum installation temperature: -5°C
- Minimum bending radius: 4 × overall cable diameter
Marking
S.Y + USE «har» H07V-R factory number.
Gammes et couleurs disponibles pour PASSEO
Charakterystyka
Charakterystyka
Konstrukcja
Konstrukcja
Rozmiar, wielkość
Rozmiar, wielkość
Parametry elektryczne
Parametry elektryczne
Parametry mechaniczne
Parametry mechaniczne
Parametry fizyczne
Parametry fizyczne
Zasoby
Zasoby
Dokumentacja
Deklaracja wykonania
- Deklaracja właściwości użytkowych nr : 1000094-FRLV
- Data certyfikacji : 11.10.2017
- AVCP(ocena i weryfikacja spojnosci i dzialania : System 3
- Jednostka notyfikowana : 1812
- Deklarowana wydajność : Eca
Nexans H07V-R 1x6 BLUE D1200m
Nexans ref. : 10164438
PEP : NXNS-00140-V02.01
- Amount of CO2 emitted Cradle to Gate phase (raw material collection and manufacturing), for the production of 1 km of cable.