N2XH 4G2.5 mm2

Description

Description

Standards

  • International
    IEC 60502-1

Application:

Used in energy networks in hotels, schools, tunnels, high constructions, hospitals, power plants, data processing centers, business centers where there is a risk of fire

 

Construction:

  1. Conductor:Copper
  2. Insulation:XLPE
  3. Filler:LSZH
  4. Outer sheath:LSZH

 

Marking:

NEXANS  IEC 60502  N2XH  Number of cores x cross section  0.6/1 kV  "YEAR"  

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Copper
Conductor shape
Circular stranded (RM)
With smaller neutral conductor
No
Insulation
XLPE (chemical)
Outer sheath
HFFR (Halogene Free Flame Retardant)
Halogen free
IEC 60754-1
Conductor flexibility
Stranded class 2
Core identification
Black, grey, blue, green / yellow
Sheath colour
Black
With Green/Yellow core
Yes

Dimensional characteristics

Dimensional characteristics

Number of cores
4
Conductor cross-section
2.5 mm²
Neutral conductor section (when smaller)
- mm²
Nominal outer diameter
12.5 mm
Approximate weight
240 kg/km

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
0,6/1 kV
Max. DC resistance of the conductor at 20°C
7.41 Ohm/km
Permissible current rating in open air
32 A
Permissible current rating when buried
30 A

Usage characteristics

Usage characteristics

Operating temperature, range
-20 ... 60 °C
Short-circuit max. conductor temperature
250 °C
Bending factor when laying
8 (xD)
Smoke density
IEC 61034
Gases corrosivity
IEC 60754-2
Flame retardant
IEC 60332-3 Cat. C
Max. conductor temperature in service
90 °C

Resources

Resources

Declaration of Performance

  • Declaration of Performance n� : 1000412-TRDE
  • Certification Date : 1/27/21
  • AVCP (Assessment and Verification of Constancy of Performance) : System 3
  • Notified body : 1008
  • Declared performance : Eca

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close